New 1kva delta ups Specifications
Model
N-1K / N-2K / N-3K
Power Rating
N-1K: 1 kVA / 0.9 kW
N-2K: 2 kVA / 1.8 kW
N-3K: 3 kVA / 2.7 kW
Input
Nominal Voltage: 220/230/240 Vac
Voltage Range: 175~280 Vac (full load), 80~175 Vac (50-100% load)
Frequency: 50/60 Hz ± 10 Hz
Power Factor: > 0.99 (full load)
Current Harmonic Distortion: < 3%
Output
Power Factor: 0.9
Voltage: 220/230/240 Vac
Frequency: 50/60 Hz ± 0.05 Hz
Voltage Harmonic Distortion: < 3% (linear load)
Overload Capability
< 105%: continuous
105~125%: 1 minute
125~150%: 30 seconds
Crest Factor: 3:1
ReceptacleN-1K: IEC C13 x 4
N-2K/3K: IEC C13 x 6, C19 x 1
Efficiency
AC-AC
N-1K: 91%
N-2K/3K: Up to 93%
Battery
Battery Voltage
N-1K: 24 Vdc
N-2K: 48 Vdc
N-3K: 72 Vdc
Typical Backup Time: 4.5 min.(full load), 13 min.(half load)
Recharge Time: 3 hrs to 90%
Charge Current: 1.5 A
Audible Noise
N-1K: < 43 dBA
N-2K/3K: < 48 dBA
Display
LCD panel
Interface
MINI Slot x 1, USB Port x 1
Comformance
Safety & EM: CCE / RCM / EN62040-1 / EN62040-2 Category C2
Physical
Dimensions (W x D x H)
N-1K: 145 x 320 x 225 mm
N-2K/3K: 190 x 390 x 325 mm
Weight
N-1K: 9 kg
N-2K: 18.6 kg
N-3K: 24.4 kg
Environment
Operating Temperature: 0~40ºC
Relative Humidity: 5~95% (non-condensing)
Runtime Table
|